Selection of Inverter for a roof top system


Image

The DC power produced is fed to inverter for conversion into AC. In a grid tied system AC power is fed to the grid at 11 KV three phase systems or to a 415V three phases or 220/240 V single phase system line depending on the system installed at institution/commercial establishment or residential complex or single house consumer and load requirement. Power generated from the solar system during the daytime is utilized fully by powering the captive loads and feeding excess power to the grid as long as grid is available. In cases, where solar power is not sufficient due to cloud cover etc. the captive loads are served by drawing power from the grid. The inverter should always give preference to the Solar Power and will use Grid/DG power only when the Solar Power is insufficient to meet the load requirement.

The output of the inverter must synchronize automatically its AC output to the exact AC voltage and frequency of the grid.

Over-voltage protection shall be provided by using Metal Oxide Varistors (MOVs) on DC and AC side the inverter.

The inverter shall be so designed so as to operate the PV system near its maximum Power Point (MPP), the operating point where the combined values  of the current and voltage of the solar modules result in a maximum power output.

The degree of protection of the indoor inverter panel shall be at least IP 31 and that of outdoor at least IP-55.

Advertisements

Leave a Reply

Please log in using one of these methods to post your comment:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s